Voltage supply
24 V AC (± 20 %) and
15…36 V DC
Power consumption
< 1.2 W/ 24 V DC; < 1.8 VA/ 24 V AC
Temperature deviation
typically ± 0.2 K at +25 °C
Sensor
Pt1000, DIN EN 60751, class B
(Perfect Sensor Protection)
Measuring range
–50...+150 °C
Zero point offset
± 10 °C
Ambient temperature
Measuring transducer –30...+70 °C
Medium
depending on selected immersion sleeve
Error detection
sensor breakage, sensor short circuit
Bus protocol
Modbus (RTU mode),
address range 0...247 selectable
Signal filtering
0,3 s / 1 s / 10 s
Protective tube
stainless steel, 1.4571, V4A, Ø = 6 mm
Electrical connection
0.2 - 1.5 mm², via push-in terminal
Cable gland
2x M 20 x 1.5; with strain relief, exchangeable,
inner diameter 8 - 13 mm
Permissible air humidity
< 95 % r. H., non-precipitating air
Protection class
III (according to EN 60 730)
Protection type
IP 65 (according to EN 60 529)*
Cable connection
cable gland, plastic
(2x M 20 x 1.5; with strain relief, exchangeable,
inner diameter 8 - 13 mm) or
M12 connector according to DIN EN 61076-2-101
(optional on request)
Internal diagnostics
Error 1 at sensor breakage
Error 2 at sensor short circuit
Housing
plastic, UV-stabilised,
material polyamide, 30 % glass-globe reinforced,
with quick-locking screws
(slotted/ Phillips head - combination),
colour traffic white (similar to RAL 9016)
Standards
CE conformity,
electromagnetic compatibility according to EN 61326,
according to EMC Directive 2014/ 30/ EU
Features
Display with illumination, three-line, programmable,
cutout approx. 51 x 29 mm (W x H),
for displaying the actual temperature or
an individually programmable display value