+386 (0)1 586 21 11, Viber: +386 41 713 243, e-mail: prodaja@termocenter.si
Pon - Pet: 8.00 -13.00 in 14.30 - 17.00; Sob, Ned, prazniki: zaprto
S+S REGELTECHNIK
TECHNICAL DETAILS
Voltage supply
24VDC via EtherCATP (US)
Power consumption
< 3 W
Temperature deviation
typically ± 0.2 K at +25 °C
Radio technology
Bluetooth (LE)
Sensor
Pt1000, DIN EN 60751, class B (Perfect Sensor Protection at IP68)
Measuring range
–50...+150 °C
Ambient temperature
Measuring transducer –30...+70 °C
Medium
clean air and
non-aggressive, non-combustible gases
Bus protocol
Sensor protection
Sensor sleeve made from stainless steel V4A (1.4571), Ø = 6 mm,
nominal length (NL) = 50 mm (optional 30...400 mm)
Process connection
Endless strap made from metal,
Ø = 13 - 92 mm (¼ - 3"), l = 300 mm (included in delivery scope)
Cable connection
M8 plug-in connector, EtherCATP-encoded
Dimensions
126 x 90 x 50 mm (Tyr 2)
Permissible air humidity
< 95 % r. H., non-precipitating air
Protection class
III (according to EN 60 730)
Standards
CE conformity, according to EMC Directive 2014/ 30/ EU,
according to RED 2014/ 53/ EU
Housing
plastic, UV-stabilised,
material polyamide, 30 % glass-globe reinforced,
with quick-locking screws
(slotted/ Phillips head - combination),
colour traffic white (similar to RAL 9016)
sensor cable
silicone, SiHF, 2 x 0.25 mm², KL = 1.5 m (other lengths and
range limits optional, e.g. PTFE leads up to +250 °C
or glass fibre with steel wire mesh up to +350°C)
Protection type
IP 65 (according to EN 60 529) sleeve humidity-tight (standard)
IP 68 (according to EN 60 529) sleeve water-tight (optional)
IP 54 (according to EN 60 529) housing / with glass fibre cable (optional)